Материал: Панель АСКВ2 7016480

Внимание! Если размещение файла нарушает Ваши авторские права, то обязательно сообщите нам

Software-specific information • OPC UA server • Description of the nodes of the information model

6.7.2.2.8 StartUpdate

Reboots the Power Panel and start the update process.

Function identical to: Service page Update → Update settings / boot logo / system (Button)

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:MethodSet/4:StartUpdate

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:Control/4:StartUpdate

Arguments for method call

Arguments -

Power Panel T50 User's manual V1.22 - Translation of the original documentation

101

Software-specific information • OPC UA server • Description of the nodes of the information model

6.7.2.3 Status

Path to the object directory:

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:Status

ns

BrowseName of the parameter

Description

Service page

R

W

4

Temperature0

Temperature of the CPU housing.

-

+

 

6.7.2.3.1 Temperature0

Temperature of the CPU housing: See "Temperature monitoring" on page 78.

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:ParameterSet/4:Temperature0

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:Status/4:Temperature0

Node attribute

NodeClass

Variable

DataType

Float

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

102

Power Panel T50 User's manual V1.22 - Translation of the original documentation

Software-specific information • OPC UA server • Description of the nodes of the information model

6.7.2.4 Identification

Path to the object directory:

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification

ns

BrowseName of the information

Description

3

CompatibilityId

ID to indicate compatibility.

2

DeviceRevision

Hardware revision of the device (e.g. C3).

2

HardwareRevision

Hardware revision of the device (e.g. C3).

2

Model

Model number of the device: e.g. 6PPT50.101E-16B.

3

ProductCode

B&R ID code (see technical data of the device).

2

RevisionCounter

Value: -1 (reserved, not in use)

2

SerialNumber

Serial number of the device (see label on back of the device).

2

SoftwareRevision

Software version of the PPT system: e.g. 1.2.0

3

VendorId

Vendor ID for customized models.

6.7.2.4.1 CompatibilityId

ID to indicate compatibility.

A future version of the device could be equipped with different technology. Although the module name and functionality of the device are identical to the previous version, the firmware may not be compatible, for example. In this case, the device reports a new CompatibilityId.

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:CompatibilityId

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/3:CompatibilityId

Node attribute

NodeClass

Variable

DataType

UInt32

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.2 DeviceRevision

Hardware revision of the device (e.g. C3).

The value of DeviceRevision is identical to the value of HardwareRevision .

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:DeviceRevision

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:DeviceRevision

Node attribute

NodeClass

Variable

DataType

String

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

Power Panel T50 User's manual V1.22 - Translation of the original documentation

103

Software-specific information • OPC UA server • Description of the nodes of the information model

6.7.2.4.3

HardwareRevision

Hardware revision of the device (e.g. C3).

The value of

HardwareRevision is identical to the value of DeviceRevision .

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:HardwareRevision

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:HardwareRevision

Node attribute

NodeClass

 

Variable

DataType

 

String

AccessLevel

 

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.4

Model

 

Model number of the device: e.g. 6PPT50.101E-16B.

See also "Model number key" on page 12.

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Model

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:Model

Node attribute

NodeClass

Variable

DataType

LocalizedText

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.5 ProductCode

B&R ID code (see technical data of the device).

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:ProductCode

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/3:ProductCode

Node attribute

NodeClass

Variable

DataType

UInt32

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.6 RevisionCounter

Value: -1 (reserved, not in use)

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:RevisionCounter

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:RevisionCounter

Node attribute

NodeClass

Variable

DataType

Int32

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

104

Power Panel T50 User's manual V1.22 - Translation of the original documentation

Software-specific information • OPC UA server • Description of the nodes of the information model

6.7.2.4.7 SerialNumber

Serial number of the device (see label on back of the device).

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:SerialNumber

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:SerialNumber

Node attribute

NodeClass

Variable

DataType

String

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.8 SoftwareRevision

Software version of the PPT system: e.g. 1.2.0

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:SoftwareRevision

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/2:SoftwareRevision

Node attribute

NodeClass

Variable

DataType

String

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

6.7.2.4.9 VendorId

Vendor ID for customized models.

VendorId Description

0B&R

1B&R

≥2 Customer ID

Path to the node (BrowsePath)

Path:

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /3:VendorId

Alternative path (function group):

0:Root/0:Objects/2:DeviceSet/4:PowerPanel T50 /2:Identification/3:VendorId

Node attribute

NodeClass

Variable

DataType

UInt32

AccessLevel

CurrentRead

UserAccessLevel

CurrentRead

Power Panel T50 User's manual V1.22 - Translation of the original documentation

105

Источник: https://studfile.net/preview/16402365/